Power Conversion System 125K (CE)
-
Safe and reliable -
High efficient operation -
Perfect compatibility -
Flexible application
- European standard production compliance and electromagnetic compatibility.
- Certificated with TUV CE certificate.
- IP6X multi protection for control cabinet.
- Adopts advanced neutral point clamped technology.
- Up to 98.5% transfer efficiency.
- Support the parallel connection of multi-machine.
- Supports lead-acid batteries, lithium batteries, etc.
- Supports battery cluster management.
- Supports RS485/Ethernet/CAN communication.
- Supports grid connection and off-grid PQ and WF operation.
- Working under 45℃ temperature with no derating.
- On-line monitoring on operational status, quickly response to.
Technical Parameters
Model
HNESPS
125-34M0
HNESPS
125-44M0
HNESPS
125-34M0Q
HNESPS
125-44M0Q
DC Voltage
650~950Vdc (Three-phase four-wire)
600~950Vdc (Three-phase three-wire)
DC Max Power
154kW
DC Max Current
222A
Overvoltage Category
Ⅱ
Rated Voltage
832V
Rated Voltage
400Vac(-15%~+15%)
Rated Frequency
50Hz(-10%~+10%)
Rated Output Current
180A
Max Output Current
228A
Rated Power
125kW
Max Output Power
150kW
Output Harmonic
<3%
Power Factor
>0.99
Power Factor Range
-1~+1
Connection
3-Phase+PE, 3-Phase+N+PE
Max Efficiency
98.5%
Overload Capacity
110%load, 10mins; 120% load, 1 min
DC Component
<0.5% (Rated output current)
Rated Output Voltage
400Vac
AC Voltage Harmonic Wavelength
<3% (Linear load)
Rated Frequency
50Hz
Rated Output Voltage
125kW
Max Apparent Power
150kVA
Max Output Current
216A
Working Temperature
-40℃~60℃(>45℃ derating)
Storage Temperature
-40℃~70℃
Humidity
0~100% (No condensing)
Altitude
4000m (>2000m derating)
Noise
<70dB
AC overcurrent protection
AC overvoltage protection, AC short-circuit protection, Anti-islanding protection, DC reverse polarity protection
Dimension 800*800*235mm
(W*D*H mm)
800*800*235mm
Installation
Vertical installation / Horizontal installation
Weight
72kg
Protection Class
Control compartment IP6X, power compartment IP20
Cooling Method
Intelligent forced air cooling
Communication Interface
RS485/Ethernet
BMS
RS485/CAN
Protocol
ModbusRTU/Modbus TCP/CAN
Display
LED, Bluetooth (Optional)