Supports lead-acid batteries, lithium batteries, etc.
Supports battery cluster management.
Supports RS485/Ethernet/CAN communication.
Based on years of accumulated grid-interactive technology (such as weak grid with poor THDU), we make our PCS more adaptable to grid-interactive applications. We also improve grid-interactive algorithm control technology based on resonance controller for better grid-interactive performance.
Technical Parameters
Model
HNESPSA125-44M0
HNESPSA125-44M0Q
Parameters for DC Side
DC Voltage
650~950Vdc (Three-phase four wire) 600~950Vdc (Three-phase three wire)
DC Max Power
150kW
DC Max Current
192A
Overvoltage Category
Ⅱ
Rated Voltage
832V
Parameter for AC Side (Grid-interactive mode)
Rated Voltage
400Vac(-15%~+15%)
Rated Frequency
50Hz(-10%~+10%)
Rated Output Current
180A
Max Output Current
228A
Rated Power
125kW
Max Output Power
150kW
Output Harmonic
<3%
Power Factor
>0.99
Power Factor Range
-1~+1
Connection
3-Phase+PE, 3-Phase+N+PE
Max Efficiency
98.5%
Overload Capacity
110%load, 10mins; 120% load, 1 min
DC Component
<0.5%(Rated output current)
Parameter for AC Side (Off-grid Mode)
Rated Output Voltage
400Vac
AC Voltage Harmonic Wavelength
<3% (Linear load))
Rated Frequency
50Hz
Rated Output Voltage
125kW
Max Apparent Power
150kVA
Max Output Current
228A
Environmental Index
Working Temperature
-40℃~60℃(>45℃ derating)
Storage Temperature
-40℃~70℃
Humidity
0~100% (No condensing)
Altitude
4000m (>2000m derating)
Noise
<70dB
Protection
AC overcurrent protection
AC overvoltage protection, AC short-circuit protection, Anti-islanding protection, DC reverse polarity protection.